Global AIDC Liquid Cooling Industry Research Report

Global AIDC Liquid Cooling Industry Research Report

全球 AI 資料中心液冷產業研究報告

Global markets, technology, supply chains and a 100 MW planning case

全球市場、技術路線、供應鏈與 100 MW 規劃案例

Complete bilingual edition with source appendix and calculation notes

完整英中雙語版 附數據來源與計算說明

Research date  November 11, 2026

研究日期 2026 年 11 月 11 日

Purpose: support industry research, supplier screening and preliminary project planning. The central finding is that competitive advantage increasingly depends on integrating reliable components, cooling systems, facility heat rejection and lifecycle services.

用途:支援產業研究、供應商篩選及專案初步規劃。核心結論是,競爭優勢越來越取決於可靠零組件、冷卻系統、設施排熱與生命週期服務的整合。

Scope: global demand and regional opportunities; technology choices; representative suppliers; procurement and risk; economics; Taiwan strategy; and a proposed 2027–2030 roadmap.

範圍:全球需求與區域機會、技術選擇、代表供應商、採購與風險、經濟性、台灣策略,以及建議的 2027–2030 年路線。

Evidence: [F] officially published information; [A] illustrative assumption; [J] research judgment. Manufacturer specifications are published claims, not independent verification. This report is not a construction design or a bankable project forecast.

資料標示:[F] 官方公開資訊;[A] 示範假設;[J] 研究判斷。廠商規格屬公開聲明,不是獨立驗證。本報告不是施工設計或銀行融資等級的專案預測。

 

 

Contents
目錄

01  Executive Summary
執行摘要

02  Global Demand and Market Definition
全球需求與市場定義

03  Regional Market Assessment
區域市場評估

04  Technology Routes and Application Fit
技術路線與適用情境

05  Global Supply Chain and Representative Suppliers
全球供應鏈與代表廠商

06  Competition Qualification and Barriers to Entry
競爭驗證與進入門檻

07  Illustrative 100 MW AIDC Cooling Case
100 MW AIDC 冷卻示範案例

08  CAPEX OPEX and Economic Evaluation
資本支出營運支出與經濟評估

09  Procurement Commissioning and Operational Risk
採購試運轉與營運風險

10  Opportunities for Taiwan Supply Chain
台灣供應鏈的全球機會

11  Proposed 2027 to 2030 Development Roadmap
2027 至 2030 年建議發展路線

12  Conclusions
結論

Appendix A  Data Sources References and Calculation Notes
附錄 A 數據出處參考文獻與計算說明

Reading guide: English appears above Traditional Chinese in paragraphs and table cells. Source codes A01–A20 refer to the clickable references in Appendix A.

閱讀說明:段落與表格儲存格均為英文在上、繁體中文在下。來源編號 A01–A20 對應附錄 A 的可點閱參考資料。

 

 

1 Executive Summary
1 執行摘要

AI data center liquid cooling is developing into an integrated industry spanning cold plates, fluid connectors, manifolds, coolant distribution units (CDUs), facility heat rejection, controls and lifecycle services. Supplier competitiveness increasingly depends on reliable deployment across this entire thermal chain.

AI 資料中心液冷正發展為涵蓋冷板、流體接頭、歧管、冷卻液分配裝置(CDU)、機房排熱、控制及全生命週期服務的整合產業。供應商競爭力,越來越取決於能否完成整條熱管理鏈的可靠部署。

[F] NVIDIA’s GB200 NVL72 combines 36 Grace CPUs and 72 Blackwell GPUs in a rack-scale liquid-cooled architecture. NVIDIA’s OCP design discussion describes approximately 120 kW of rack cooling capacity. This is a platform-specific reference, not a universal design value. [A04–A05]

[F] NVIDIA GB200 NVL72 採用機櫃級液冷架構,整合 36 顆 Grace CPU 與 72 顆 Blackwell GPU;其 OCP 設計說明提到約 120 kW 的機櫃冷卻能力。此為特定平台參考,不能作為所有機櫃的通用設計值。[A04–A05]

[J] The strongest commercial opportunities lie in qualified cooling components, integrated CDU and fluid networks, facility retrofits and recurring maintenance services. Product announcements alone do not establish customer qualification, shipment volume or profitability.

[J] 較具發展價值的商業機會包括通過驗證的冷卻零組件、CDU 與流體管網整合、既有機房改造,以及持續性維護服務。產品發表本身,不足以證明已取得客戶認證、形成出貨規模或實現獲利。

2 Global Demand and Market Definition
2 全球需求與市場定義

[F] The IEA’s 2026 update reports that global data center electricity demand increased by 17% in 2025, while electricity consumption by AI-focused data centers increased by 50%. These figures indicate infrastructure expansion; they are not liquid-cooling revenue growth rates. [A01]

[F] IEA 2026 年更新指出,2025 年全球資料中心用電需求增加 17%,其中 AI 導向資料中心用電增加 50%。這些數據反映基礎設施擴張,並非液冷市場營收成長率。[A01]

[F] The IEA’s 2025 baseline estimated global data center electricity use at 415 TWh in 2024, with the United States accounting for 45%, China 25% and Europe 15%. These historical shares provide geographic context, not regional liquid-cooling market shares. [A02]

[F] IEA 2025 年報告估計,2024 年全球資料中心用電為 415 TWh,其中美國占 45%、中國占 25%、歐洲占 15%。此歷史分布可作為區域需求背景,不能直接視為各地液冷市場占比。[A02]

For market sizing, four revenue pools should be separated to prevent double counting.

估算市場規模時,應區分以下四類收入,避免重複計算。

Revenue pool
收入類別
Included scope
納入範圍
Double counting risk
重複計算風險
IT-side components
IT 側零組件
Cold plates, hoses, connectors and rack manifolds
冷板、軟管、接頭及機櫃歧管
May already be included in server prices
可能已包含在伺服器售價
Cooling systems
冷卻系統
CDUs, rear-door exchangers and immersion equipment
CDU、後門熱交換器及浸沒設備
Internal pumps and exchangers may be counted twice
內部泵浦與換熱器可能重複加總
Facility infrastructure
設施基礎工程
Piping, heat rejection, controls and installation
管網、排熱、控制及安裝
Equipment may already be included in EPC contracts
設備可能已包含在統包合約
Lifecycle services
生命週期服務
Commissioning, maintenance, fluid testing and spares
試運轉、維護、流體檢測及備品
Warranty and service bundles may overlap
保固與維護套裝可能重疊

 

[J] A defensible global estimate should disclose technology scope, revenue boundary, base year and treatment of installation and services. This report does not adopt a single global market value or CAGR without a comparable underlying definition.

[J] 可查核的全球估值應揭露技術範圍、收入邊界、基準年度,以及安裝和服務的計算方式。本報告不採用缺乏一致定義的單一全球市場金額或年複合成長率。

3 Regional Market Assessment
3 區域市場評估

[F] The IEA’s 2025 regional outlook projected that the United States and China would account for nearly 80% of global data center electricity-demand growth through 2030. Southeast Asian demand was projected to more than double by 2030. These remain projections from the 2025 report. [A03]

[F] IEA 2025 年區域展望預估,美國與中國將占截至 2030 年全球資料中心新增用電需求的近 80%;東南亞需求預期在 2030 年前增加至兩倍以上。此為 2025 年報告的預測。[A03]

The regional table is a strategic assessment [J], not a measured market-share ranking.

下表為策略性評估 [J],並非經量測的市占率排名。

Region
區域
Commercial focus
商業重點
Deployment considerations
部署考量
United States and Canada
美國與加拿大
Hyperscale AI clusters, integrated cooling and lifecycle support
超大規模 AI 叢集、整合冷卻及生命週期服務
Available power, schedules, local service and redundancy
可用電力、時程、在地服務與備援
Europe
歐洲
Efficient cooling, retrofits and suitable heat-reuse projects
高效率冷卻、改造及適合的廢熱利用
Climate, water, heat users and project requirements
氣候、水資源、熱需求端及專案要求
China
中國
Domestic computing platforms and locally integrated supply chains
國產運算平台及在地供應鏈整合
Platform compatibility, procurement and service capability
平台相容性、採購及服務能力
Taiwan
台灣
Components, server integration, validation and exports
零組件、伺服器整合、驗證及出口
Overseas service, quality and customer concentration
海外服務、品質及客戶集中度
Japan and South Korea
日本與韓國
High-reliability AI and enterprise infrastructure
高可靠度 AI 與企業基礎設施
Space, seismic conditions, retrofit and response time
空間、地震條件、改造及回應時間
Southeast Asia
東南亞
New facilities and regional cloud expansion
新建機房與區域雲端擴張
Hot and humid climate, water and full-year performance
高溫高濕、水資源及全年性能
Middle East
中東
Large AI campuses and integrated delivery
大型 AI 園區及整合交付
High outdoor temperatures, dust, water and maintenance
室外高溫、沙塵、水資源及維護
Latin America including Brazil
拉丁美洲包括巴西
Selective new builds and regional partnerships
具條件的新建案及區域合作
Grid access, import logistics, spares and commissioning
接電、進口物流、備品及試運轉

 

Regional opportunity must be evaluated at project level. Attractive national energy resources do not automatically establish available power, suitable land or sufficient cooling infrastructure at a specific site.

區域商機須落實到個別專案評估。國家具有良好能源條件,不代表特定場址已具備可用電力、適合土地或足夠冷卻設施。

4 Technology Routes and Application Fit
4 技術路線與適用情境

Technology
技術
Operating principle
運作原理
Application and constraints
應用與限制
Direct-to-chip cold plates
晶片直接冷板液冷
Liquid removes heat through a cold plate attached to the package
液體經貼附封裝的冷板帶走熱量
High-density servers; validated thermal and hydraulic interfaces required
高密度伺服器;須驗證熱傳與水力介面
Liquid-to-liquid CDU
液對液 CDU
Transfers heat between IT coolant and facility water
IT 冷卻液與設施水之間換熱
Needs facility water and adequate heat rejection
須具設施水與足夠排熱能力
Liquid-to-air CDU
液對氣 CDU
Rejects coolant heat into air
將冷卻液熱量排至空氣
Selected retrofits; uses available air-cooling capacity
部分改造;占用可用氣冷容量
Rear-door heat exchanger
後門熱交換器
Captures heat from rack exhaust air
攔截機櫃排風熱量
Mixed environments; check airflow, pressure and access
混合環境;確認氣流、壓力及維修空間
Single-phase immersion
單相浸沒式
Equipment immersed in non-boiling dielectric fluid
設備浸於不沸騰介電液
Equipment, material and maintenance compatibility required
須確認設備、材料與維修相容性
Two-phase immersion
雙相浸沒式
Boiling and condensation of a working fluid
工作流體沸騰及冷凝
Fluid containment and lifecycle planning required
須規劃流體密閉與生命週期管理

 

OCP’s cold-plate work covers the technology cooling system from the cold plate to the CDU, reinforcing the need to validate the full liquid path rather than individual parts in isolation. [A07–A08]

OCP 冷板工作項目涵蓋從冷板到 CDU 的技術冷卻系統,顯示驗證完整液體路徑的重要性,而不能只分別確認單一零件。[A07–A08]

Liquid cooling does not automatically eliminate air cooling or chillers. HPE’s GB200 NVL72 documentation describes combined air and liquid cooling. Chiller requirements depend on climate, allowable supply temperature and facility design. [A06]

液冷不會自動消除氣冷或冷凍機需求。HPE 的 GB200 NVL72 文件描述氣冷與液冷混合架構。是否需要冷凍機,取決於氣候、容許供液溫度及機房設計。[A06]

5 Global Supply Chain and Representative Suppliers
5 全球供應鏈與代表廠商

The following suppliers have relevant official product information identified in this research. Inclusion does not establish market leadership or qualification for every platform.

以下廠商具有本次研究查得的官方產品資訊。列入名單不代表市占排名,也不代表已通過所有平台驗證。

Supplier
廠商
Published coverage
公開產品範圍
Position and sources
定位與來源
Delta Electronics
台達電
Cold plates and liquid-to-air/liquid-to-liquid CDUs
冷板、液對氣與液對液 CDU
Power and thermal integration
電力與熱管理整合 [A12–A13]
Auras
雙鴻
Cold plates, connectors, manifolds, RPU and CDUs
冷板、接頭、歧管、RPU 與 CDU
Modules to systems
由模組至系統 [A14]
Cooler Master
訊凱
Cold plates, manifolds and large CDUs
冷板、歧管及大型 CDU
Components and infrastructure
零組件與基礎設施 [A15]
Kaori
高力
Data center heat exchangers and cooling solutions
資料中心熱交換器及冷卻方案
Heat-transfer applications
熱交換應用 [A16]
Vertiv CDUs, fluid networks, heat rejection, controls and services
CDU、流體管網、排熱、控制及服務
Thermal-chain integration
熱管理鏈整合 [A17–A18]
Schneider Electric / Motivair
施耐德/Motivair
CDUs, cold plates, rear-door exchangers and chillers
CDU、冷板、後門換熱器及冷凍機
Facility-to-chip integration
設施至晶片整合 [A19]
Trane Technologies / LiquidStack Direct-to-chip and immersion cooling with facility HVAC
直接液冷、浸沒式與設施空調
Plant and IT-side convergence
主機與 IT 側整合 [A20]
CPC / Danfoss Liquid-cooling quick disconnects
液冷快速接頭
Fluid-interface reliability
流體介面可靠度 [A09–A10]
Global Tek
時碩
UQD liquid-cooling connectors
UQD 液冷接頭
Precision components
精密零組件 [A11]

 

Corporate structure matters when mapping competitors. Schneider Electric acquired a controlling interest in Motivair in February 2025. Trane Technologies announced completion of its LiquidStack acquisition on March 3, 2026. [A19–A20]

分析競爭關係時,必須辨識集團結構。施耐德於 2025 年 2 月取得 Motivair 控股權;Trane Technologies 於 2026 年 3 月 3 日宣布完成收購 LiquidStack。[A19–A20]

The uploaded supply-chain map is a research lead, not an approved-vendor list. Unchecked entries, including supplier-specific platform and shipment claims, require individual verification. CPC has published UQD/UQDB products and should not be treated solely as an unspecified alternative connector vendor. [A09]

上傳供應鏈圖僅作研究線索,不是合格供應商名單。未查核項目,包括個別廠商平台與出貨聲明,仍須逐一驗證。CPC 已公開 UQD/UQDB 產品,不宜僅列為未明確分類的替代接頭廠商。[A09]

6 Competition Qualification and Barriers to Entry
6 競爭驗證與進入門檻

[J] Competitive advantage depends on thermal performance, manufacturing consistency, interoperability and field support. A low purchase price cannot compensate for poor reliability or delayed commissioning.

[J] 競爭優勢取決於熱性能、製造一致性、互通性及現場服務。低採購價格無法彌補可靠度不足或試運轉延誤。

Segment
環節
Main barrier
主要門檻
Evidence to request
應要求的證據
Cold plate
冷板
Thermal resistance, pressure drop and process quality
熱阻、壓降及製程品質
Tested performance across the operating envelope
完整操作範圍測試性能
Quick disconnect
快速接頭
Sealing, mating life and fluid compatibility
密封、插拔壽命及流體相容性
Pair-specific test data and specification revision
配對測試及規格版本
CDU Heat exchange, controls and failure response
換熱、控制及故障反應
Performance curves and degraded-mode capacity
性能曲線及降級容量
Manifold and piping
歧管與管路
Cleanliness, balancing and installation quality
潔淨度、平衡及施工品質
Cleaning, pressure and flow-test records
清洗、壓力及流量測試紀錄
System integration
系統整合
Interfaces and commissioning
介面及試運轉
Integrated acceptance and responsibility matrix
整合驗收及責任矩陣
Services
服務
Skills, spares and response coverage
技能、備品及回應範圍
Service levels and parts availability
服務水準及備品可用性

 

Qualification must be recorded at model level. Vertiv’s September 2026 announcement identifies a specific 2.3 MW CDU as NVIDIA DSX Ready; this must not be generalized to every product in the portfolio. [A18]

驗證狀態必須記錄到型號層級。Vertiv 2026 年 9 月公告特定 2.3 MW CDU 取得 NVIDIA DSX Ready 資格,不可擴張到其全部產品。[A18]

7 Illustrative 100 MW AIDC Cooling Case
7 100 MW AIDC 冷卻示範案例

[A] This case illustrates scale. It is not a construction design, quotation or site-specific feasibility conclusion.

[A] 本案例用於說明規模,並非施工設計、報價或特定場址可行性結論。

Parameter
參數
Assumption
假設
Full IT load
IT 滿載負載
100 MW
IT heat captured by liquid
液體帶走的 IT 熱量比例
85%
Liquid-side IT heat load
液冷側 IT 熱負載
85 MW
Remaining IT heat load
其餘 IT 熱負載
15 MW
Coolant temperature rise
供回液溫差
10°C
Specific heat approximation
比熱近似值
4.18 kJ/kg·K
Effective CDU capacity at design conditions
設計工況 CDU 有效容量
2 MW/unit
2 MW/台

 

Heat balance: Q = ṁ × cₚ × ΔT. At 85,000 kW and a 10°C rise, ṁ = 85,000 ÷ (4.18 × 10) = 2,033.49 kg/s. With water-like density, combined flow is approximately 7,320 m³/h across all liquid-cooling zones.

熱平衡:Q = ṁ × cₚ × ΔT。在 85,000 kW 及 10°C 溫升下,ṁ = 85,000 ÷ (4.18 × 10) = 2,033.49 kg/s。以近似水的密度計算,全部液冷分區合計流量約 7,320 m³/h。

Glycol concentration and actual coolant properties change the required flow and pumping performance. The calculated flow is not the flow of a single pipe.

乙二醇等添加劑濃度及實際流體性質,會改變所需流量與泵浦性能。計算所得並非單一管路流量。

At 2 MW effective capacity per CDU, simple load division gives 43 operating units. Installed quantity must add zone-level redundancy, maintenance isolation and derating. One spare CDU for the whole facility does not automatically provide redundancy to every zone.

若每台 CDU 有效容量為 2 MW,按負載相除需 43 台運轉設備。實際數量須加入分區備援、維修隔離及降額。全場多設一台 CDU,不代表每個分區均獲得備援。

The 85 MW liquid load and 15 MW remaining IT load exclude additional facility losses. Final heat rejection must account for relevant pump, fan, electrical and other heat gains. Appendix A provides the reproducible calculations.

85 MW 液冷及 15 MW 其餘 IT 負載,未包含額外設施損失。最終排熱須納入相關泵浦、風機、電氣及其他熱源。附錄 A 提供可重算過程。

8 CAPEX OPEX and Economic Evaluation
8 資本支出營運支出與經濟評估

Cooling economics should be compared at equal delivered computing output and availability. PUE alone does not measure the full business benefit.

冷卻經濟性應在相同有效運算產出與可用率下比較。PUE 無法單獨衡量完整商業效益。

Cost category
成本類別
Scope
範圍
IT-side CAPEX
IT 側資本支出
Cold plates, hoses, connectors and manifolds
冷板、軟管、接頭及歧管
Cooling-system CAPEX
冷卻系統資本支出
CDUs, pumps, exchangers and monitoring
CDU、泵浦、熱交換器及監控
Facility CAPEX
設施資本支出
Piping, heat rejection, electrical works and civil modifications
管網、排熱、電氣工程及土建改造
Deployment cost
部署成本
Engineering, cleaning, testing and commissioning
設計、清洗、測試及試運轉
Operating cost
營運成本
Electricity, water, fluids, maintenance and spare parts
電力、水、冷卻液、維護及備品
Availability cost
可用率成本
Planned downtime, failures and performance restrictions
計畫停機、故障及性能限制

 

[A] If average IT load is 100 MW and a measured PUE reduction of 0.05 is achieved under comparable conditions, annual electricity savings are 100 × 0.05 × 8,760 = 43,800 MWh. At an assumed US$0.10/kWh, electricity-cost savings are US$4.38 million annually.

[A] 若平均 IT 負載為 100 MW,且在可比較條件下實測 PUE 降低 0.05,年節電量為 100 × 0.05 × 8,760 = 43,800 MWh。假設電價每 kWh 0.10 美元,每年電費節省為 438 萬美元。

This sensitivity calculation is not a promised liquid-cooling saving or project profit. It excludes incremental CAPEX and changes in water, maintenance, financing, taxes and replacement costs. Actual benefits require hourly load, weather and system-efficiency analysis.

此敏感度計算不是液冷保證節省或專案利潤,未計新增資本支出及水費、維護、融資、稅務、汰換成本變化。實際效益須依逐時負載、氣象及系統效率分析。

9 Procurement Commissioning and Operational Risk
9 採購試運轉與營運風險

Compare CDUs at identical facility-water temperature, coolant temperature, fluid mixture, flow and pressure conditions. Nameplate megawatts alone are insufficient. Cooler Master’s published 1.4 MW CDU lists a 5°C approach temperature difference and maximum secondary flow, illustrating why capacity must be read with its conditions. [A15]

比較 CDU 應統一設施水溫、冷卻液溫度、配方、流量與壓力。只比較銘牌 MW 並不足夠。Cooler Master 1.4 MW CDU 列出 5°C 接近溫差及最大二次側流量,說明容量須連同工況判讀。[A15]

Risk
風險
Control or verification
控制或驗證
Leakage
漏液
Detection, location, isolation and tested response logic
偵測、定位、隔離及經測試的反應邏輯
Corrosion or contamination
腐蝕或污染
Materials review, cleaning and fluid-quality monitoring
材料審查、清洗及流體品質監測
Flow imbalance
流量不均
Hydraulic analysis and commissioning measurements
水力分析及試運轉量測
Pump or power failure
泵浦或電源故障
Redundant paths and validated transient response
備援路徑及暫態反應驗證
Condensation
結露
Supply-temperature control relative to dew point
供液溫度與露點的控制
Interface mismatch
介面不相容
Model-level compatibility and paired-component tests
型號層級相容性及配對零件測試
Unclear responsibility
責任不清
Define IT, CDU, piping and facility vendor boundaries
明定 IT、CDU、管網及設施廠商責任
Inadequate acceptance testing
驗收測試不足
Representative liquid heat loads and integrated fault scenarios
具代表性的液體熱負載及整合故障情境

 

[J] Acceptance must demonstrate heat removal, hydraulic balance, control behavior, failure recovery and maintainability. Delivery is only one milestone in operational readiness. Contract documents should specify performance boundaries, test conditions, acceptance criteria, spare parts and service response.

[J] 驗收須證明排熱能力、水力平衡、控制行為、故障復原及可維修性。交貨只是可營運準備的其中一項里程碑。合約應明定性能邊界、測試工況、驗收標準、備品及服務回應。

10 Opportunities for Taiwan Supply Chain
10 台灣供應鏈的全球機會

[J] Taiwan’s practical opportunity is to combine precision thermal components with server integration and overseas engineering services. Exporting validated subsystems can create more value than selling unqualified components separately.

[J] 台灣務實的機會,是結合精密散熱零組件、伺服器整合及海外工程服務。輸出經驗證子系統,可能比各自銷售未完成整合驗證的零件創造更高價值。

Business model
商業模式
Offering
交付內容
Capability to build
應建立能力
Component supplier
零組件供應商
Cold plates, connectors, manifolds and exchangers
冷板、接頭、歧管及熱交換器
Process control, traceability and qualification
製程控制、追溯及驗證
Validated subsystem supplier
驗證子系統供應商
Matched cold plate, hose, connector and manifold assemblies
冷板、軟管、接頭與歧管配套
Thermal, hydraulic and reliability testing
熱、水力及可靠度測試
CDU or rack solution provider
CDU 或機櫃方案商
Equipment, controls and integration documentation
設備、控制及整合文件
Software, failure handling and interoperability
軟體、故障處理及互通性
Overseas engineering partner
海外工程合作商
Installation, flushing, filling and commissioning
安裝、清洗、充液及試運轉
Local teams, project management and field quality
在地團隊、專案管理及現場品質
Lifecycle service provider
生命週期服務商
Maintenance, fluid testing, spares and monitoring
維護、流體檢測、備品及監控
Coverage, diagnostic data and spare logistics
服務範圍、診斷資料及備品物流

 

Identify the actual buyer: server OEM/ODM, rack integrator, hyperscaler, colocation operator or engineering contractor. Each purchases a different scope and assigns different warranty responsibilities.

應確認實際買方:伺服器 OEM/ODM、機櫃整合商、超大規模雲端業者、主機託管業者或工程承包商。不同買方採購範圍與保固責任均不同。

11 Proposed 2027 to 2030 Development Roadmap
11 2027 至 2030 年建議發展路線

This roadmap is a proposed execution strategy [J], not guaranteed industry adoption or a confirmed supplier commitment.

本路線為建議執行策略 [J],並非產業必然採用的預測或已確認廠商承諾。

Period
期間
Priority
優先工作
Deliverable
交付成果
2027 Product qualification and reference installations
產品驗證及示範場域
Test reports, compatible assemblies and operating references
測試報告、相容組件及運轉案例
2028 Overseas installation and service
海外安裝與服務
Regional partners, spares and service agreements
區域夥伴、備品及服務合約
2029 Coordinated cooling and workload monitoring
冷卻與運算負載協同監測
Validated controls and measured improvements
經驗證控制及實測改善
2030 Fleet-scale lifecycle optimization
多場址生命週期最佳化
Reliability benchmarks and refurbishment or replacement plans
可靠度比較及翻修、汰換計畫

 

Automation must remain within verified equipment limits and protection functions. Optimization benefits must be demonstrated using operating data.

自動化應遵守已驗證設備操作限制與保護功能,最佳化效益須以實際營運資料證明。

12 Conclusions
12 結論

The global opportunity is supported by expanding AI infrastructure and rising rack-level thermal requirements. Data center growth cannot be converted directly into liquid-cooling revenue without defining adoption, equipment scope and project timing.

全球機會受到 AI 基礎設施擴張及機櫃熱需求提高的支持。若未定義液冷採用比例、設備範圍及專案時程,不能將資料中心成長直接換算為液冷營收。

[J] Successful suppliers will combine qualified products, consistent manufacturing, clear system responsibility and dependable field services. For a 100 MW project, the decisive issue is whether the complete cooling chain can deliver required capacity during normal operation, faults and maintenance.

[J] 成功供應商將結合通過驗證的產品、穩定製造、明確系統責任及可靠現場服務。對 100 MW 專案而言,決定性問題是完整冷卻鏈能否在正常運轉、故障與維修時提供所需能力。

For Taiwan, the strategic priority is to turn component strength into globally deployable and verifiable cooling systems and services.

對台灣而言,策略重點是將零組件優勢轉化為可在全球部署、可驗證的冷卻系統與服務。

 

 

Appendix A Data Sources References and Calculation Notes
附錄 A 數據出處參考文獻與計算說明

Source review date: November 11, 2026. Publication dates are included where confirmed. Product pages may change; retain dated datasheets for procurement. English source titles are followed by Chinese descriptions.

查閱日期:2026 年 11 月 11 日。已確認者列發布日期。產品頁可能更新,採購應保存具日期的型錄版本。英文來源名稱下列中文說明。

A1 Global market and electricity demand
A1 全球市場與用電需求

A01  IEA — Key Questions on Energy and AI — Executive Summary

IEA《能源與 AI 關鍵問題》執行摘要 | 2026

Global data center electricity demand grew 17% in 2025; AI-focused demand grew 50%. These are electricity-growth figures, not cooling revenue growth.

2025 年全球資料中心用電增加 17%,AI 導向需求增加 50%。屬用電成長,不是液冷營收成長。

Official source / 官方來源

A02  IEA — Energy and AI — Executive Summary

IEA《能源與 AI》執行摘要 | 2025

2024 electricity estimate: 415 TWh; United States 45%, China 25%, Europe 15%. Covers all data centers, not only AI or liquid-cooled sites.

2024 年用電估計 415 TWh;美國 45%、中國 25%、歐洲 15%。涵蓋全部資料中心,不限 AI 或液冷。

Official source / 官方來源

A03  IEA — Energy and AI — Energy Demand from AI

IEA《能源與 AI》之 AI 能源需求章節 | 2025

United States and China: nearly 80% of projected growth to 2030; Southeast Asian demand more than doubles. These are 2025 projections, not observed 2030 outcomes.

美國與中國占至 2030 年預估新增需求近 80%;東南亞需求增加至兩倍以上。屬 2025 年預測,不是 2030 年實績。

Official source / 官方來源

A2 Computing platforms and cooling requirements
A2 運算平台與冷卻需求

A04  NVIDIA — GB200 NVL72

NVIDIA GB200 NVL72 官方產品頁 | Product page / 產品頁

36 Grace CPUs and 72 Blackwell GPUs in a rack-scale liquid-cooled architecture. Specific to the named platform.

36 顆 Grace CPU 與 72 顆 Blackwell GPU,採機櫃級液冷。適用於所列平台。

Official source / 官方來源

A05  NVIDIA — NVIDIA Contributes NVIDIA GB200 NVL72 Designs to Open Compute Project

NVIDIA 向 OCP 提供 GB200 NVL72 設計的技術文章 | Technical blog / 技術文章

Describes 120 kW rack cooling capacity. Not a universal rack rating; electrical and thermal requirements vary by configuration.

描述 120 kW 機櫃冷卻能力。不是通用額定值;電力與熱需求依組態而異。

Official source / 官方來源

A06  HPE — NVIDIA GB200 NVL72 by HPE

HPE GB200 NVL72 官方產品頁 | Product page / 產品頁

Combined air and liquid cooling. Does not establish the illustrative 85% liquid heat-capture ratio.

採氣冷與液冷混合方式。未建立示範案例的 85% 液冷熱捕獲比例。

Official source / 官方來源

A3 Cooling standards and component interfaces
A3 冷卻規格與零組件介面

A07  Open Compute Project — Cold Plate

OCP 冷板專案 | Project page / 專案頁

Covers the technology cooling system from cold plate to CDU. Project scope is not product certification.

涵蓋冷板至 CDU 的技術冷卻系統。專案範圍不等於產品認證。

Official source / 官方來源

A08  Open Compute Project — Cooling Environments

OCP 冷卻環境專案 | Project page / 專案頁

Cooling work and UQD resources. Procurement must identify specification revision and actual connector pairs.

冷卻工作及 UQD 資源。採購須指定規格版本及實際接頭配對。

Official source / 官方來源

A09  CPC — Everis UQD06 and UQDB06

CPC Everis UQD06 與 UQDB06 接頭 | Product page / 產品頁

Published UQD/UQDB products. Availability does not establish unrestricted cross-brand interchangeability.

公開 UQD/UQDB 產品。產品存在不代表可跨品牌無條件互換。

Official source / 官方來源

A10  Danfoss — Universal Quick Disconnect Couplings for Data Center Liquid Cooling

Danfoss 資料中心液冷通用快速接頭公告 | Official announcement / 官方公告

Data center UQD couplings. Verify model-specific pressure, temperature, flow and compatibility.

資料中心 UQD 接頭。須查核型號壓力、溫度、流量及相容性。

Official source / 官方來源

A11  Global Tek — Universal Quick Disconnect

時碩液冷快插型快速接頭 | Product page / 產品頁

Evidence of UQD product positioning, not proof of shipment volume or customer qualification.

證明 UQD 產品布局,不代表出貨量或客戶驗證。

Official source / 官方來源

A4 Supplier products and published capacity
A4 廠商產品與公開容量

A12  Delta — Liquid Cooling Solution

台達液冷方案 | Product overview / 產品總覽

Cold plates and liquid-cooling solutions support the supplier-coverage table.

冷板及液冷方案,支持供應商產品範圍表。

Official source / 官方來源

A13  Delta — Data Center Cooling and GoCool 3 MW Shipping Announcement

台達資料中心冷卻及 GoCool 3 MW 出貨公告 | 2026 announcement / 2026 年公告

Liquid-to-air and liquid-to-liquid CDU portfolio; 3 MW shipping announcement. Shipment statement is manufacturer-reported.

液對氣與液對液 CDU 組合,以及 3 MW 出貨公告。出貨為廠商聲明。

Official source / 官方來源

Delta product portfolio / 台達產品組合

A14  Auras — Official Corporate Presentation

雙鴻官方公司簡報 | Official PDF / 官方 PDF

Lists cold plates, connectors, manifolds, RPU and CDU configurations. Does not quantify shipments for each category.

列示冷板、接頭、歧管、RPU 及 CDU 配置。未據此量化各類出貨。

Official source / 官方來源

A15  Cooler Master — 1.4 MW Liquid-to-Liquid In-Row CDU

Cooler Master 1.4 MW 液對液列間 CDU | Product specification / 產品規格

Published 1,400 kW capacity, 5°C approach temperature difference and 1,500 L/min maximum secondary flow. Read all ratings with their operating conditions.

公開 1,400 kW 容量、5°C 接近溫差及最大二次側流量 1,500 L/min。各項額定值須連同工況判讀。

Official source / 官方來源

A16  Kaori — Data Center Cooling

高力資料中心冷卻 | Product page / 產品頁

Data center heat exchangers and liquid-cooling applications. Product coverage does not establish market share.

資料中心熱交換器及液冷應用。產品範圍不代表市占率。

Official source / 官方來源

A17  Vertiv — Expands Liquid Cooling Portfolio in EMEA

Vertiv 擴充 EMEA 液冷產品組合 | 2026-05-26

100 kW to 2.3 MW CDU range and fluid-network row manifolds. Published ratings require condition-matched comparison.

100 kW 至 2.3 MW CDU 範圍及列間流體歧管。公開容量須在相同工況比較。

Official source / 官方來源

A18  Vertiv — Coolant Distribution Unit Qualified as NVIDIA DSX Ready

Vertiv CDU 取得 NVIDIA DSX Ready 資格 | 2026-09-21

Specific 2.3 MW model announced as DSX Ready. Do not extend qualification to the entire portfolio.

特定 2.3 MW 型號公告取得資格,不可擴張至全部產品。

Official source / 官方來源

A5 Corporate transactions and integration
A5 企業交易與整合

A19  Schneider Electric — Liquid Cooling Portfolio with Motivair

施耐德攜手 Motivair 發表液冷產品組合 | Taiwan release 2025-10-02 / 台灣公告

Controlling interest in Motivair acquired in February 2025; integrated portfolio includes CDUs, cold plates, rear-door exchangers and chillers. Controlling interest is not automatically full ownership.

2025 年 2 月取得 Motivair 控股權;產品涵蓋 CDU、冷板、後門換熱器及冷凍機。控股權不自動等於完全持有。

Official source / 官方來源

A20  Trane Technologies — Completes Acquisition of LiquidStack

Trane Technologies 完成收購 LiquidStack | 2026-03-03

Completed acquisition supports corporate-integration analysis, not a market-share claim.

完成收購支持企業整合分析,不是市占率證明。

Official source / 官方來源

Citation note: the report combines 2024 estimates, 2025 growth observations and projections published in 2025. Retain their individual years rather than presenting them as one 2026 market dataset. Maximum product ratings must not be assumed to occur simultaneously.

引用說明:報告合併使用 2024 年估計、2025 年成長觀察及 2025 年發布的預測,應保留各自年度,不宜統稱同一組 2026 年市場數據。產品各項最大值不可假設同時達成。

A6 Assumption register
A6 假設登錄表

These inputs are illustrative, not project measurements, manufacturer quotations or official market averages. Calculated outputs inherit the limitations of the inputs.

以下輸入為示範設定,不是專案實測、廠商報價或官方市場平均。計算結果承接輸入假設的限制。

Item
項目
Value
數值
Basis
依據
IT design load
IT 設計負載
100 MW [A] Selected project scale
選定專案規模
Liquid heat capture
液冷熱捕獲
85% [A] Requires equipment-specific verification
須依設備驗證
Liquid IT heat
液冷 IT 熱量
85 MW Calculated: 100 × 85%
計算值
Remaining IT heat
其餘 IT 熱量
15 MW Calculated: 100 − 85
計算值
Coolant temperature rise
冷卻液溫升
10°C [A] Illustrative design condition
示範設計條件
Specific heat
比熱
4.18 kJ/kg·K [A] Water-like approximation, not specified fluid data
近似水,不是指定冷卻液資料
Density
密度
≈1,000 kg/m³ [A] Volume-flow conversion approximation
體積流量換算近似值
Effective CDU capacity
CDU 有效容量
2 MW/unit
2 MW/台
[A] No model selected
未選定型號
Average IT load in savings case
節電案例平均 IT 負載
100 MW [A] Full-year average assumption
全年平均假設
PUE reduction
PUE 降幅
0.05 [A] Sensitivity input, not guaranteed
敏感度輸入,非保證
Electricity price
電價
US$0.10/kWh [A] Not a country-specific quotation
非特定國家報價
Annual hours
全年時數
8,760 h 365 × 24; non-leap year
非閏年全年基準

 

A7 Reproducible calculations
A7 可重算的計算過程

A7.1 Steady-state sensible heat balance and coolant flow

A7.1 穩態顯熱平衡及冷卻液流量

Q = ṁ × cₚ × ΔT
ṁ = 85,000 kJ/s ÷ (4.18 kJ/kg·K × 10 K) = 2,033.49 kg/s
V̇ = (2,033.49 ÷ 1,000) × 3,600 = 7,320.57 m³/h

Rounded total: approximately 7,320 m³/h across all zones. Excludes detailed pressure losses, variation in coolant properties and additional facility heat gains.

取整合計約 7,320 m³/h,涵蓋全部分區。未含詳細壓損、流體性質變化及額外設施熱負載。

A7.2 CDU operating quantity

A7.2 CDU 運轉台數

N = ceiling(85 MW ÷ 2 MW/unit) = 43 units

Thermal-capacity minimum only. Redundancy, zoning, maintenance isolation and derating must be added separately.

僅為熱容量最低數量,備援、分區、維修隔離與降額須另計。

A7.3 Annual electricity savings at equal average IT load and comparable measurement boundaries

A7.3 相同平均 IT 負載及可比較量測邊界下的年節電

ΔE = P_IT,avg × ΔPUE × t
ΔE = 100 MW × 0.05 × 8,760 h = 43,800 MWh/year

A7.4 Annual electricity-cost savings

A7.4 年電費節省

43,800 MWh × 1,000 kWh/MWh × US$0.10/kWh = US$4,380,000/year

Electricity-cost savings only, not profit or net cash flow. Incremental CAPEX, water, maintenance, financing, taxes and replacement costs are excluded.

僅為電費節省,不是利潤或淨現金流;未扣新增資本支出、水費、維護、融資、稅務及汰換成本。

A8 Research judgments and unverified items
A8 研究判斷與尚未驗證項目

Report element
報告項目
Evidence status
證據狀態
Regional opportunities and entry priorities
區域商機與進入優先順序
[J] Qualitative assessment, not revenue ranking
定性評估,不是營收排名
Barriers and attractive business models
門檻與商業模式
[J] Engineering and commercial interpretation
工程與商業分析
Taiwan strategy
台灣策略
[J] Proposed strategic direction
建議策略方向
2027–2030 roadmap
2027–2030 路線
[J] Proposed sequence, not confirmed industry commitments
建議順序,非已確認產業承諾
Global liquid-cooling value and CAGR
全球液冷金額與 CAGR
Not established in this report
本報告未建立估值
Supplier shares, revenues and shipment volumes
廠商市占、營收及出貨量
Not established by product pages
產品頁不足以證明
Unchecked original supplier-map entries
原圖未逐一查核名單
Research leads, not an approved-vendor list
研究線索,非合格供應商名單

 

Recommended citation format: organization, document or page title, publication date where available, URL and access date. For procurement, retain the actual datasheet revision, qualification evidence and performance conditions in addition to webpage references.

建議引用格式:機構、文件或網頁名稱、發布日期(如有)、網址及查閱日期。用於採購時,除網頁來源,還應保存實際型錄版本、驗證證據及性能工況。