800V AI Server Detailed Design
800V AI 伺服器詳細設計文件
10U chassis 8 GPUs
10U 機箱 八顆 GPU
Revision 0.1 | 24 October 2026 | Engineering requirements and preliminary design
版本 0.1|2026 年 10 月 24 日|工程需求與初步設計
This document establishes a reviewable design basis for an 800V DC server. It specifies module responsibilities, interfaces, calculations and verification evidence. Architecture A and B remain alternatives until GPU, rack power and cooling requirements are frozen.
本文件建立可供審查的 800V 直流伺服器設計基準,定義模組責任、介面、計算與驗證證據。在 GPU、機櫃供電及冷卻需求凍結前,架構 A 與 B 均保留為候選。
Status: proposed design, not released for fabrication. The rendering is illustrative; component count, routing, spacing and cold-plate geometry must follow the engineering drawings. No existing GPU platform is claimed to accept 800V directly.
狀態:提案設計,尚未發行製造。產品圖僅為示意;零件數量、走線、間距與冷板幾何須以工程圖為準。不宣稱任何既有 GPU 平台可直接接入 800V。
01 Scope and Design Control
01 範圍與設計管制
The product boundary runs from the server HV connector to GPU, CPU, memory, storage and network rails, including local auxiliary power, cooling interfaces and management. Rack rectification, upstream protection and the CDU are external systems with mandatory interface agreements.
產品邊界由伺服器高壓連接器至 GPU、CPU、記憶體、儲存與網路供電軌,包含輔助電源、冷卻接口與管理。機櫃整流、上游保護及 CDU 為外部系統,必須簽定介面規格。
| Basis 基準 |
Defined or pending 已定義或待確認 |
| Fixed scope 固定範圍 |
10U enclosure; 8 GPUs; nominal 800V DC input. 10U 機箱、8 GPU、標稱 800V 直流輸入。 |
| Design options 設計選項 |
A: 800V to 50V; B: 800V to 12V class. A:800V 降至 50V;B:800V 降至 12V 級。 |
| Open requirements 待定需求 |
GPU model, transient load, rail limits, input range, grounding, rack fault current, redundancy, coolant and ambient envelope. GPU 型號、瞬態負載、電源軌限制、輸入範圍、接地、機櫃故障電流、備援、冷卻液及環境範圍。 |
| Evidence classes 證據分類 |
REQ: proposed requirement; CALC: illustrative calculation; REF: public engineering evidence; TBD: unresolved. REQ:提議需求;CALC:示例計算;REF:公開工程證據;TBD:尚待決定。 |
Release conditions
發行條件
Release schematics only after input and load envelopes are approved. Release PCB and mechanics after insulation, thermal and current-path reviews. Release manufacturing files after design verification, fault testing and configuration control. A module rating alone does not release a server design.
輸入與負載範圍核准後才能發行電路圖;絕緣、熱與電流路徑審查完成後發行 PCB 與機構;設計驗證、故障測試及組態管制完成後發行製造資料。單一模組額定值不能作為整機放行依據。
Document map
文件導覽
Sections 02–04: power budget, architecture and mechanics. Sections 05–08: HV protection, pre-charge and conversion. Sections 09–12: GPU rails, cooling, controls and service. Sections 13–16: verification, BOM, release actions and references.
第 02–04 節:功率預算、架構與機構。第 05–08 節:高壓保護、預充與轉換。第 09–12 節:GPU 供電、冷卻、控制與維修。第 13–16 節:驗證、BOM、發行行動與來源。
02 Power Budget and Operating Envelope
02 功率預算與操作範圍
CALC example only: allocate 1.2kW per GPU, 0.8kW for CPUs and memory, 0.6kW for network and storage, and 0.5kW for fans and auxiliaries. Delivered rail power is 11.5kW. These are planning assumptions, not vendor TDP values.
CALC 僅作示例:每 GPU 配置 1.2kW,CPU 與記憶體共 0.8kW,網路與儲存 0.6kW,風扇與輔助設備 0.5kW;供至各電源軌合計 11.5kW。這些是規劃假設,並非供應商 TDP。
| Parameter 參數 |
Calculation 計算 |
Implication 含義 |
| Delivered rails 電源軌功率 |
8 × 1.2 + 0.8 + 0.6 + 0.5 = 11.5kW | Sum actual maximum loads. 須加總實際最大負載。 |
| Illustrative end to end efficiency 假設端到端效率 |
95% | Includes all conversion paths in this example. 本例包含各轉換路徑。 |
| HV input 高壓輸入 |
11.5 / 0.95 = 12.105kW | Loss = 605W 損失為 605W |
| Nominal input current 標稱輸入電流 |
12.105kW / 800V = 15.13A | Not a connector rating. 不是連接器額定值。 |
| Planning capacity 規劃容量 |
12.105 × 1.2 = 14.53kW | 20% example margin; excludes redundancy sizing. 20% 示例餘裕;不含備援容量。 |
Use Iin,max = Pout,max /(Vin,min × ηmin). Add transient, tolerance, derating and current-sharing effects separately. Do not apply a peak converter efficiency to every load point. Specify continuous, peak-duration and startup envelopes independently.
採用 Iin,max=Pout,max/(Vin,min × ηmin)。瞬態、公差、降額與均流效應另行計入。不能將轉換器峰值效率套用全部負載。連續、峰值持續時間及啟動範圍必須分別定義。
Eight GPUs require a coordinated rack power cap. Firmware must limit aggregate loading during startup and workload transitions, but hardware protection must still contain a controller or software failure.
八顆 GPU 需要協調機櫃功率上限。韌體須限制啟動及工作負載切換時的總負載,但硬體保護仍須能處理控制器或軟體失效。
03 Candidate Power Architectures
03 候選供電架構
Architecture A
架構 A
800V inlet → coordinated protection and pre-charge → isolated 800V to 50V conversion → zonal 50V distribution → local low-voltage conversion where required → POL → device rails. The exact intermediate rail follows the GPU board specification.
800V 入口 → 協調保護與預充 → 隔離式 800V 降至 50V → 分區 50V 配電 → 視需要就地低壓轉換 → POL → 元件電源軌。實際中間電壓依 GPU 板規格決定。
Architecture B
架構 B
800V inlet → coordinated protection and pre-charge → isolated conversion to a 12V-class rail near each load zone → local POL → device rails. Avoid a long shared 12V trunk. A 12.5V prototype is not automatically compatible with a nominal 12V platform.
800V 入口 → 協調保護與預充 → 負載分區附近隔離轉換至 12V 級 → 就地 POL → 元件電源軌。避免長距離共用 12V 主幹;12.5V 原型不代表能直接相容標稱 12V 平台。
| Criterion 比較項 |
Architecture A 架構 A |
Architecture B 架構 B |
| Placement 配置 |
Flexible 50V distribution 50V 配電較有彈性 |
Converters close to loads 轉換器貼近負載 |
| Loss drivers 損失來源 |
Extra conversion and 50V path 額外轉換及 50V 路徑 |
High current joints and copper 大電流接點及銅材 |
| Cooling 冷卻 |
Distributed heat sources 熱源可分區 |
Concentrated converter heat 轉換熱源集中 |
| Acceptance 驗收 |
Full HV to device rail measurement 高壓至元件電源軌完整量測 |
Same endpoints and cooling 相同端點及冷卻比較 |
CALC: 98.1% × 98.5% = 96.63%; versus an assumed direct stage at 97%, the crossover downstream efficiency is 97/98.1 = 98.88%. This is a conditional stage comparison, excluding protection, distribution and POL. Choose using measured complete-path losses and service constraints.
CALC:98.1% × 98.5%=96.63%;相對假設直接轉換為 97%,後級效率交叉點為 97/98.1=98.88%。這是排除保護、配電與 POL 的條件式級間比較。最終應依完整路徑實測損失及維修限制選型。
04 Mechanical Layout and Interface Control
04 機構配置與介面管制
Reserve distinct HV, compute and coolant service zones. Treat the conceptual 2 × 4 GPU arrangement as a packaging study; vendor interconnect and substrate constraints may require a different physical layout. Verify 10U fit with rail hardware, cable bends and service travel.
配置獨立高壓、運算及冷卻維修區。2 × 4 GPU 只作封裝配置研究;供應商互連與基板限制可能要求不同佈局。10U 相容性須包含滑軌、線材彎曲及維修抽拉行程。
| Interface ID 介面編號 |
Definition required 應定義內容 |
Owner 責任 |
| IF01 HV inlet 高壓入口 |
Poles, polarity, PE, touch protection, interlock, voltage and fault ratings 極數、極性、PE、防觸電、連鎖、電壓與故障額定 |
Power and rack 電源與機櫃 |
| IF02 LV output 低壓輸出 |
Rail tolerance, ripple, load step, capacitance, reverse current, sense points 電壓公差、漣波、負載階躍、電容、逆流、感測點 |
Power and GPU 電源與 GPU |
| IF03 Cooling 冷卻 |
Fluid, pressure, flow, temperatures, QD type, materials, leak detection 流體、壓力、流量、溫度、快接、材質、漏液偵測 |
Thermal and CDU 熱設計與 CDU |
| IF04 Management 管理 |
Isolation, pinout, address, register map, alarms and fail state 隔離、腳位、位址、暫存器、警報與失效狀態 |
BMC and power BMC 與電源 |
| IF05 Mechanics 機構 |
Datum, tolerance stack, mass, centre of gravity, insertion force and retention 基準、公差鏈、重量、重心、插入力及固定 |
Mechanical 機構 |
Locate liquid joints away from exposed HV surfaces and include controlled drainage or barriers. Chassis bonding must survive module replacement. Any connector claimed for live insertion needs the specific mating sequence and DC interruption capability validated; a mechanical fit alone is insufficient.
液體接點應避開裸露高壓表面,並設計排液或隔板。機殼搭接須在模組更換後保持有效。任何宣稱可帶電插拔的連接器,都須驗證插拔順序與直流切斷能力;機構可插合並不充分。
05 High Voltage Input and Protection
05 高壓入口與保護
REQ HV01: define whether the rack uses a two-wire 800V bus, a bipolar bus or another arrangement. Specify conductor-to-chassis stresses, fault return paths and all live conductors to be disconnected. Protective earth is distinct from the DC return.
REQ HV01:定義機櫃採兩線式 800V、雙極母線或其他架構。列明導體對機殼應力、故障回流路徑及須切斷的全部帶電導體。保護接地與直流回路不同。
REQ HV02: combine upstream DC-rated protection, local fast electronic protection, controlled pre-charge, residual-energy discharge and sensing. Select the order and location by fault-zone analysis. An eFuse or semiconductor switch does not by itself provide a service isolation gap.
REQ HV02:結合上游直流額定保護、本地快速電子保護、受控預充、殘能放電及感測。順序與位置依故障區分析決定。eFuse 或半導體開關本身不構成維修隔離間隙。
| Event 事件 |
Required response 要求處置 |
Evidence 證據 |
| Output short 輸出短路 |
Limit energy and interrupt within validated device SOA; prevent backfeed 在已驗證 SOA 內限制能量並切斷,防止回灌 |
Current, VDS and timing traces 電流、VDS 與時序波形 |
| Switch stuck on 開關短路失效 |
Independent upstream or series disconnect path; inhibit restart 獨立上游或串聯切斷路徑,禁止重啟 |
Single fault test 單一故障測試 |
| Over or undervoltage 過壓或欠壓 |
Block start or shut down with hysteresis and controlled recovery 禁止啟動或關機,設遲滯與受控恢復 |
Threshold and ramp sweep 門檻與斜率掃描 |
| Control supply loss 控制電源消失 |
Defined off behavior including normally-on JFET bias dependencies 定義關斷行為,納入常開 JFET 偏壓相依 |
Loss-of-bias test 偏壓消失測試 |
Coordinate local and upstream protection across minimum and maximum prospective fault currents and bus inductance. Record interruption overshoot, clamp energy, fuse I²t and clearing selectivity. Specify reverse-energy paths from parallel modules and charged output capacitors.
以最小及最大預期故障電流與母線電感協調本地和上游保護。記錄切斷過衝、箝位能量、熔絲 I²t 及選擇性。明列並聯模組與輸出電容的反向供能路徑。
06 Precharge and Residual Energy
06 預充與殘留能量
REQ PC01: converters remain disabled during pre-charge. Start only after input validity, interlocks and sensor plausibility pass. Ramp current under the switch SOA and thermal limits; qualify the final voltage difference and slope before enabling conversion. Timeout or abnormal slope latches a fault.
REQ PC01:預充期間停用轉換器。輸入、連鎖及感測合理性通過後才開始。依開關 SOA 與熱限制升流;確認最終壓差及斜率後才允許轉換。逾時或異常斜率須鎖定故障。
| CALC example 計算示例 |
Result 結果 |
| C = 300µF, V = 800V, t = 1.5s; ideal constant current 理想定電流預充 |
I = C × V / t = 0.16A |
| Capacitor stored energy 電容儲能 |
E = ½CV² = 96J |
| Fixed bus and disabled load 固定母線且負載停用 |
Series-path dissipation ≈ 96J 串聯路徑耗散約 96J |
| Initial and average switch power 初始及平均開關耗散 |
Pinitial = 128W; Pavg = 64W 初始 128W;平均 64W |
| Scaling to 1mF with same time 相同時間擴至 1mF |
0.533A and 320J stored; ≈320J series loss 0.533A、儲能 320J、串聯耗散約 320J |
These equations omit tolerances, load leakage and switching dynamics. Validate hot-case SOA using the actual VDS–ID trajectory, transient thermal impedance and repeated-start cooldown. A published 300µF test cannot qualify a larger server capacitance. [1][2]
上述公式未含公差、負載漏電及切換動態。須以實際 VDS–ID 軌跡、暫態熱阻及重複啟動冷卻間隔驗證熱態 SOA。公開的 300µF 測試不能直接認證更大整機電容。[1][2]
For passive discharge, V(t)=V0 exp(−t/RC), so R ≤ t/[C ln(V0/Vrelease)]. Define Vrelease and release time through the applicable safety assessment, not an assumed universal threshold. Rate resistor pulse energy, initial power V0²/R and open-circuit failure; measure residual voltage independently before service.
被動放電採 V(t)=V0 exp(−t/RC),故 R ≤ t/[C ln(V0/Vrelease)]。維修放行電壓及時間須由適用安全評估定義,不能假設通用門檻。驗證電阻脈衝能量、初始功率 V0²/R 與開路失效,維修前獨立量測殘壓。
07 Isolated Conversion and Magnetic Design
07 隔離轉換與磁性設計
A candidate implementation uses input-series output-parallel modules. Series connection reduces nominal module input stress, but startup, imbalance and one-module failure can create unequal voltages. A 650V device must not be placed directly across an 800V bus without a topology that bounds its worst-case stress.
候選實作採輸入串聯、輸出並聯模組。串聯降低標稱模組輸入應力,但啟動、失衡及單模組失效會造成不均分壓。650V 元件不能直接跨接 800V 母線,除非拓撲能限制其最壞應力。
| Design requirement 設計要求 |
Review evidence 審查證據 |
| CV01 Voltage sharing 分壓 |
Startup, shutdown, open and short module cases; tolerances and balancing losses 啟停、模組開短路、公差及平衡損失。 |
| CV02 Output sharing 輸出均流 |
Cable/contact mismatch, thermal drift, circulating current and reverse blocking 線材接點差異、熱漂移、循環電流及逆流阻擋。 |
| CV03 Magnetics 磁性元件 |
Flux over the operating envelope, core/copper losses, leakage, insulation and winding temperature 操作範圍磁通、鐵銅損、漏感、絕緣及繞組溫度。 |
| CV04 Resonant operation 諧振操作 |
Gain, soft-switching range, dead time, parasitics and abnormal startup 增益、軟切換範圍、死區、寄生及異常啟動。 |
| CV05 Insulation 絕緣 |
Working/transient voltage, pollution, material, altitude and accessible circuits 工作與暫態電壓、污染、材質、海拔與可接觸電路。 |
A fixed-ratio DCX does not regulate a constant rail. CALC: an ideal 64:1 ratio with 760–840V input produces 11.875–13.125V. This assumed input range must be approved; the GPU board must tolerate the resulting rail or another regulation stage is required.
固定變比 DCX 不會保持恆定輸出。CALC:理想 64:1 變比、輸入 760–840V 時,輸出為 11.875–13.125V。此假設輸入範圍須核准;GPU 板必須容許其變動,否則須增加穩壓級。
Define conducted and radiated emission test setups, common-mode return paths and isolation capacitance. Safety spacing and dielectric test levels remain TBD pending compliance engineering; they cannot be inferred solely from nominal 800V.
定義傳導與輻射測試配置、共模回流及隔離電容。安全間距與耐壓測試值待合規工程確認,不能僅由標稱 800V 推定。
08 SiC GaN and Silicon Selection
08 SiC GaN 與矽元件選型
| Function 功能 |
Candidate 候選 |
Selection evidence 選型證據 |
| HV pre-charge and interruption 高壓預充與切斷 |
SiC JFET cascode plus controller SiC JFET cascode 與控制器 |
Linear SOA, bias loss behavior, short-circuit energy, retries and thermal path 線性 SOA、失偏壓行為、短路能量、重試與熱路徑。 |
| HF primary conversion 高頻一次側轉換 |
GaN with bounded voltage stress 受控電壓應力下的 GaN |
Switching loss, dv/dt immunity, driver loop, overshoot and package thermal limits 切換損失、dv/dt 耐受、驅動迴路、過衝與封裝熱限制。 |
| Secondary rectification 二次側整流 |
Si or GaN 矽或 GaN |
Conduction loss, dead time, commutation, parallel sharing and cost 導通損失、死區、換流、並聯均流與成本。 |
| GPU POL GPU 負載端穩壓 |
Qualified multiphase Si or GaN stage 經驗證多相矽或 GaN 功率級 |
Vendor rail requirements, load step, package inductance and cooling 原廠電源軌要求、負載階躍、封裝電感與冷卻。 |
| Control and sensing 控制與感測 |
Controller, isolation and sensors 控制器、隔離與感測器 |
Accuracy across temperature, isolation and deterministic fault response 全溫精度、隔離及確定性故障反應。 |
REF: public engineering literature supports a SiC JFET cascode for high-voltage protection and GaN in high-frequency conversion. The paper also uses silicon in secondary rectification; no material is mandated for every stage. [1]
REF:公開工程文獻支持 SiC JFET cascode 高壓保護及 GaN 高頻轉換;論文也使用矽元件作二次側整流,並非每一級都指定同一材料。[1]
Infineon announced XDP8HD40S-1 in October 2026 for high-voltage power-path protection and monitoring. Treat it as a sourcing candidate, not a drop-in replacement for the paper’s controller. Obtain the complete datasheet, supported external switch configuration, samples and qualification evidence before design freeze. [3]
Infineon 於 2026 年 10 月公布 XDP8HD40S-1 高壓電源路徑保護與監測控制器。此為採購候選,不是論文控制器的直接替換。設計凍結前須取得完整規格、支援外部開關配置、樣品及資格證據。[3]
09 GPU Board and Point of Load Regulation
09 GPU 運算板與負載端穩壓
REQ GPU01: obtain the selected accelerator platform’s rail table, sequence, voltage tolerance, ripple limits, load-step waveform, power cap behavior and management interface. Do not design core voltage or phase count from GPU TDP alone. Preserve vendor high-speed interconnect topology and mechanical keep-outs.
REQ GPU01:取得選定加速器平台的電源軌表、時序、電壓公差、漣波、負載階躍、功率限制及管理介面。不能只由 GPU TDP 決定核心電壓或相數。保留原廠高速互連拓撲與機構禁布區。
| Requirement 要求 |
Implementation and check 實作與檢查 |
| GPU02 Local regulation 就地穩壓 |
Place POL and decoupling close to load; verify DC drop and transient impedance at specified sense points. POL 與去耦靠近負載;於指定感測點驗證直流壓降及瞬態阻抗。 |
| GPU03 Sequencing 上電時序 |
Auxiliary rails and power-good first; enable GPU rails only after input and cooling readiness. 先建立輔助供電與 power-good;輸入及冷卻就緒後啟用 GPU 電源軌。 |
| GPU04 Fault zones 故障分區 |
Define per-GPU or grouped protection, backfeed paths and coordinated host shutdown. 定義逐 GPU 或群組保護、回灌路徑與協調主機關機。 |
| GPU05 Power transients 功率瞬態 |
Test simultaneous and staggered load steps, idle-to-maximum and workload oscillation. 測試同步及錯開階躍、待機至最大負載及工作負載振盪。 |
CALC at 1.2kW per GPU before local regulation: ideal current is 24A at 50V, 96A at 12.5V and 100A at 12V. Eight 12V branches total 800A. Use local branches rather than assuming one connector carries the aggregate current. Actual current includes downstream losses.
CALC:每 GPU 在本地穩壓前為 1.2kW,理想電流在 50V 為 24A、12.5V 為 96A、12V 為 100A。八支 12V 分路合計 800A;採本地分路,不假設由單一連接器承載總電流。實際值還須包含後級損失。
Use ΔV = I × R for steady drop and ΔV ≈ ΔI × ESR + ΔI × Δt/C as a first transient estimate. Complete frequency-domain and time-domain checks with regulator response, ESL and package impedance. Remote-sense open/short faults must not drive overvoltage.
穩態壓降採 ΔV=I × R;瞬態初估採 ΔV ≈ ΔI × ESR+ΔI × Δt/C。納入穩壓器響應、ESL 及封裝阻抗完成頻域與時域驗證。遠端感測開短路不得導致過壓。
10 Liquid Cooling and Thermal Design
10 液冷與熱設計
REQ TH01: cold plates cover the selected GPU package contact areas; power modules and magnetics receive separately validated cooling paths. Residual air cooling remains necessary for memory, NICs, storage, connectors and unplated components unless their heat is captured elsewhere.
REQ TH01:冷板涵蓋所選 GPU 封裝接觸面;電源模組與磁性元件的冷卻路徑另行驗證。記憶體、NIC、儲存、連接器及未覆冷板元件,除非另有散熱路徑,仍須空氣冷卻。
CALC: for 12kW captured by liquid, water approximation cp = 4.18kJ/(kg·K) and a 10K rise gives mass flow Q/(cpΔT) = 0.287kg/s, approximately 17.2L/min. This is a heat-balance example, not a specified pump flow. Actual coolant properties, branch distribution and pressure drop govern the design.
CALC:液體帶走 12kW 熱量,採水比熱約 4.18kJ/(kg·K)、升溫 10K,質量流率 Q/(cpΔT)=0.287kg/s,約 17.2L/min。此為熱平衡示例,不是泵流量規格;實際設計依冷卻液物性、支路分流及壓降決定。
| Check 檢查 |
Required evidence 要求證據 |
| Hydraulic 水力 |
Pressure-flow curve for all branches, QDs and manifold; worst branch flow and blocked-branch behavior 全支路、快接及歧管壓流曲線;最弱支路及堵塞行為。 |
| Thermal 熱 |
Junction and case estimates at maximum inlet temperature, minimum flow, aged TIM and component tolerances 最高入口溫度、最低流量、老化 TIM 及公差下的接面與殼溫。 |
| Materials 材質 |
Coolant compatibility, galvanic corrosion, seals, particles and maintenance interval 冷卻液相容、電偶腐蝕、密封、微粒與維護週期。 |
| Abnormal cooling 異常冷卻 |
Leak, pump loss, flow sensor failure, condensation and fan failure responses 漏液、停泵、流量感測失效、結露及風扇故障反應。 |
Set warning, throttling and shutdown thresholds from thermal characterization and sensor delay. Flow loss must trigger a response fast enough for local thermal capacitance; average outlet temperature cannot alone protect a single blocked GPU branch.
警告、降載與關機門檻須由熱特性及感測延遲決定。流量消失的反應速度須符合局部熱容量;平均出口溫度不能單獨保護被堵塞的 GPU 支路。
11 Control States and Telemetry
11 控制狀態與遙測
| State 狀態 |
Entry and action 進入與動作 |
Exit 離開條件 |
| S0 Isolated 隔離 |
Main power off; residual energy monitored 主電力關閉,監測殘能 |
Service closed and authorized 維修關閉且授權 |
| S1 Check 檢查 |
Validate auxiliary, bus, sensors, cooling and interlock 驗證輔助電源、母線、感測、冷卻及連鎖 |
All checks pass 全部通過 |
| S2 Pre-charge 預充 |
Converters disabled; controlled current ramp 轉換器停用,受控電流斜升 |
Voltage and slope qualified 電壓與斜率合格 |
| S3 Ready 待命 |
Establish intermediate rails and power-good 建立中間電源軌及就緒訊號 |
Host enable 主機允許 |
| S4 Run 運行 |
Enable rails; monitor limits; manage power cap 啟用電源軌、監控限制、管理功率 |
Stop request or fault 停機要求或故障 |
| S5 Discharge 放電 |
Disable load, disconnect source, discharge 停負載、切來源、放電 |
Residual voltage verified 殘壓確認 |
| SF Latched fault 故障鎖定 |
Fast hardware action; retain fault context 快速硬體動作,保留故障資訊 |
Authorized reset and recheck 授權重設後重檢 |
Asynchronous hardware faults override normal sequencing. Classify communication loss as a controlled fallback, sensor implausibility as a safety-related fault, and maintenance interlock opening as a power-removal request. Define restart permissions per fault; repeated blind retries are prohibited.
非同步硬體故障優先於一般時序。通訊消失採受控降級,感測不合理列為安全相關故障,維修連鎖開啟則要求移除電力。逐故障定義重啟權限,禁止無條件反覆重試。
Telemetry shall include HV input/output voltage, input current, module currents, device temperatures, coolant inlet/outlet temperature, flow, leak state, interlock, pre-charge duration and fault counters. Each field needs unit, range, accuracy, update interval, timestamp and invalid-data behavior. Fast protection remains local hardware; BMC logging is not the interruption loop.
遙測須含高壓輸入輸出電壓、輸入電流、模組電流、元件溫度、冷卻進出口溫度、流量、漏液、連鎖、預充時間及故障計數。每欄定義單位、範圍、精度、更新間隔、時間戳及無效資料行為。快速保護由本地硬體執行,BMC 記錄不作切斷迴路。
12 Service Isolation and Fault Containment
12 維修隔離與故障限制
REQ SV01: define the replaceable units and whether replacement requires server shutdown or a validated live-rack procedure. Keeping adjacent servers running does not mean the serviced module is energized. Establish an isolation boundary that prevents alternate feeds and output backfeed.
REQ SV01:定義可更換單元,以及更換是否須停整機或使用已驗證的帶電機櫃程序。相鄰伺服器持續運轉不代表被維修模組仍帶電。隔離邊界須防止替代來源及輸出回灌。
| Fault 故障 |
Containment action 限制措施 |
Service implication 維修要求 |
| HV switch short 高壓開關短路 |
Independent disconnection and fault latch 獨立切斷並鎖定 |
Do not rely on software off 不可依賴軟體關閉 |
| Converter short 轉換器短路 |
Zone protection, reverse isolation, upstream selectivity 分區保護、反向隔離、上游選擇性 |
Inspect source and load damage 檢查來源及負載損傷 |
| Liquid leak 漏液 |
Remove affected power using validated response; maintain event record 依已驗證反應切受影響電源並留紀錄 |
Inspect and qualify before restart 檢查合格後才重啟 |
| Discharge path open 放電路徑開路 |
Detect residual voltage; inhibit access release 偵測殘壓,禁止放行 |
Use approved recovery procedure 依核准程序處置 |
| Sensor or BMC failure 感測或 BMC 故障 |
Hardware protection and defined degraded state 硬體保護與明確降級 |
No automatic assumption of safety 不能自動視為安全 |
Service sequence: stop workloads and confirm rail shutdown; isolate all relevant sources; secure against re-energization; discharge and verify absence of hazardous voltage with the approved method; isolate coolant if needed; replace the unit; restore bonding and interlocks; perform post-service checks and controlled pre-charge. Qualified service procedures must define the actual measurement points and instruments.
維修順序:停止工作負載並確認電源軌關閉;隔離所有相關來源;防止再送電;依核准方法放電並確認無危險電壓;視需要隔離冷卻;更換單元;恢復搭接與連鎖;執行維修後檢查及受控預充。合格維修程序須指定實際量測點及儀器。
13 Verification and Acceptance Matrix
13 驗證與驗收矩陣
Every test report shall retain hardware/BOM revision, firmware, instrument calibration, input impedance, coolant conditions, load waveform and uncertainty. Numerical acceptance limits remain tied to approved requirements; TBD limits must be closed before formal qualification.
每份測試報告須保留硬體與 BOM 版本、韌體、儀器校正、輸入阻抗、冷卻條件、負載波形及量測不確定度。數值驗收門檻依核准需求;正式資格驗證前必須關閉 TBD。
| Test ID 編號 |
Condition and measurement 條件與量測 |
Acceptance basis 驗收依據 |
| V01 / HV01 | Input min/max and polarity; conductor-to-chassis faults 輸入極值、極性及導體對機殼故障 |
No unsafe stress or accessible energy 無不安全應力或可接觸能量 |
| V02 / PC01 | Cold/hot start, max C, restart and timeout 冷熱啟動、最大電容、重啟與逾時 |
SOA and temperature within approved limits SOA 與溫度符合核准限制 |
| V03 / HV02 | Minimum/maximum fault current and inductance 故障電流與電感極值 |
Contained failure and selectivity 故障受控且符合選擇性 |
| V04 / CV01–04 | Sharing, load sweep, module loss and fixed-ratio range 分壓均流、負載掃描、模組消失及變比範圍 |
All device and rail limits met 符合元件與電源軌限制 |
| V05 / GPU02–05 | Simultaneous GPU load steps and sensing faults GPU 同步階躍與感測故障 |
Rail tolerance and host stability 電壓公差與主機穩定 |
| V06 / TH01 | Worst inlet/flow; blocked branch; fan/pump loss 最差入口與流量、堵支路、停風扇停泵 |
Thermal limits and timely action 熱限制與及時處置 |
| V07 / SV01 | Interlock, discharge failure, alternate backfeed 連鎖、放電失效、其他回灌 |
Access blocked until release criteria met 符合放行條件才允許接近 |
| V08 / System | Dielectric, bonding, EMC, cycling and endurance 耐壓、搭接、EMC、循環及耐久 |
Applicable standards and approved test plan 適用標準與核准計畫 |
Measure complete-system efficiency with synchronized power boundaries and calibrated instruments; identify whether fan, pump and auxiliary power is included. Report a load curve and uncertainty, not only peak efficiency. Endurance duration, sample size and allowable failures require a reliability plan.
完整系統效率須同步量測邊界並使用校正儀器;說明風扇、泵及輔助電源是否計入。提供負載曲線及不確定度,不能只報峰值效率。耐久時間、樣本數與容許故障數須由可靠度計畫定義。
14 Preliminary BOM and Supplier Deliverables
14 初步 BOM 與供應商交付
| Item 項目 |
Quantity basis 數量基準 |
Required supplier data 供應商資料 |
| GPU modules GPU 模組 |
8 | Platform rail and thermal specifications 平台電源軌與熱規格 |
| HV inlet assembly 高壓入口組件 |
Per selected feed arrangement 依進線配置 |
DC ratings, mating sequence, insulation, temperature rise 直流額定、插拔順序、絕緣、溫升 |
| Protection/pre-charge board 保護預充板 |
Per fault zone 依故障分區 |
SOA, startup/fault waveforms, controller and switch BOM SOA、啟動故障波形、控制及開關 BOM |
| Isolated converters 隔離轉換器 |
N satisfying derated capacity N 須符合降額容量 |
Full efficiency map, current sharing, transient range 完整效率圖、均流及瞬態範圍 |
| POL assemblies 負載端穩壓組件 |
By vendor rail and phase needs 依原廠電源軌與相數 |
Rail compliance, load-step data, firmware compatibility 電源軌符合性、階躍資料、韌體相容 |
| Cold plates and manifold 冷板及歧管 |
8 GPU interfaces plus other heat sources 8 GPU 接觸面另加其他熱源 |
Pressure-flow map, thermal resistance and leak qualification 壓流圖、熱阻及漏液驗證 |
| Sensors and BMC interface 感測及 BMC 介面 |
By monitoring points 依監測點 |
Accuracy, isolation, calibration and register map 精度、隔離、校正及暫存器表 |
| Chassis and interconnect 機箱與互連 |
1 chassis; paths by zone 1 機箱;路徑依分區 |
Tolerance, bonding, busbar/contact loss and service life 公差、搭接、匯流排接點損失及壽命 |
Capacity rule: N × Pmodule,derated ≥ Prequired. If N+1 is required, validate (N−1) × Pmodule,derated ≥ Prequired together with post-fault current sharing, cooling and topology behavior. Input-series modules may fail as a group; arithmetic spare capacity does not prove redundancy.
容量規則:N × Pmodule,derated ≥ Prequired。若要求 N+1,須驗證 (N−1) × Pmodule,derated ≥ Prequired,並檢查故障後均流、冷卻及拓撲。輸入串聯模組可能成組失效,算術備用容量不等於已證明備援。
15 Engineering Deliverables and Open Decisions
15 工程交付與待決策事項
| Gate 關卡 |
Deliverables 交付 |
Release decision 放行決策 |
| G1 Requirements 需求 |
GPU and rack interface specification; power and thermal envelope; architecture comparison GPU 與機櫃介面規格、功率熱範圍、架構比較 |
Choose A or B and close critical TBDs 選 A 或 B 並關閉關鍵 TBD |
| G2 Design review 設計審查 |
Schematics, PCB stackup and layout, insulation map, magnetic design, mechanical CAD, FMEA 電路圖、PCB 疊構佈局、絕緣圖、磁性、機構 CAD、FMEA |
Approve prototype build 核准原型製作 |
| G3 Verification 設計驗證 |
V01–V08 results, thermal/EMC fixes, firmware state tests, supplier qualification V01–V08 結果、熱與 EMC 修正、韌體狀態測試、供應商資格 |
Approve pilot configuration 核准試點組態 |
| G4 Production 量產 |
Controlled BOM, drawings, test fixtures, calibration, traceability, service manual and yield criteria 受控 BOM、圖面、測試治具、校正、追溯、維修手冊及良率門檻 |
Manufacturing and quality signoff 製造與品質簽核 |
Decisions that block schematic release
阻礙電路圖發行的決策
Power architect: approve input range, topology, grounding and prospective fault current. GPU/platform owner: freeze accelerator type, rail envelope and load transients. Thermal owner: approve coolant, flow/pressure limits and inlet range. Mechanical owner: approve rack, mass and service interfaces. Compliance owner: establish applicable editions and test conditions.
電源架構負責人:核准輸入範圍、拓撲、接地及預期故障電流。GPU/平台負責人:凍結加速器型號、電源軌範圍及負載瞬態。熱設計負責人:核准冷卻液、流壓限制與入口範圍。機構負責人:核准機櫃、重量及維修介面。合規負責人:建立適用版本與測試條件。
This revision provides detailed requirements and sizing methods. Fabrication-ready schematics, pin assignments, component values, Gerbers, winding drawings, tolerance drawings and signed test limits require the above decisions and engineering analysis. Maintain each open item with an owner, due date and closure evidence.
本版提供詳細需求與估算方法。可製造電路圖、腳位、元件值、Gerber、繞線圖、公差圖及簽核測試門檻,須以上述決策及工程分析完成。每項未決事項須指定責任人、期限及關閉證據。
16 References and Evidence Boundaries
16 參考資料與證據邊界
[1] Kasper et al. Power Conversion Solutions for Future Server Boards Operating Directly From High-Voltage DC. CPSS TPEA 11(1), 2026. DOI 10.24295/CPSSTPEA.2026.00003.
https://tpea.cpss.org.cn/uploads/allimg/260330/10.24295CPSSTPEA.2026.00003.pdf
[2] onsemi. AND90399/D EliteSiC JFET Based High Voltage Hot-Swap Application. December 2025 Rev 0.
https://www.onsemi.com/download/application-notes/pdf/and90399-d.pdf
[3] Infineon. XDP8HD40S-1 high-voltage hot-swap controller. 12 October 2026 announcement and product page.
https://www.infineon.com/technology-news/2026/inftn202610-006
[4] Infineon. MGX AI Factory ecosystem and power delivery. 29 May 2026 webpage.
https://www.infineon.com/press-release/2026/infxx202605-092
[5] IEC. IEC 62368-1:2023 product safety standard catalog, corrected version noted August 2025.
https://webstore.iec.ch/en/publication/69308
Sources checked on 24 October 2026. Public papers support feasibility under their prototype conditions; supplier announcements establish product direction, not this server’s qualification. Equations and scenario budgets in this document are independent engineering calculations.
來源查核日期為 2026 年 10 月 24 日。公開論文支持其原型條件下的可行性;供應商公告證明產品方向,並非本伺服器通過驗證。本文公式及情境預算為獨立工程計算。
The paper’s 300µF / approximately 1.5s abstract example and 150µF / approximately 210ms main-text waveform use different conditions. Its 98.13% full-load result concerns a 400V-to-50V 3kW submodule; the approximately 97% 6kW result concerns a 12.5V nominal prototype with liquid cooling. None is a complete 10U server efficiency rating. [1]
論文摘要 300µF/約 1.5 秒與正文 150µF/約 210ms 波形屬不同條件。98.13% 滿載結果屬 400V→50V、3kW 子模組;約 97% 的 6kW 結果屬標稱 12.5V 液冷原型。均不是完整 10U 伺服器效率額定。[1]
IEC 62368-1 provides a safety framework; this document does not reproduce its normative requirements or claim certification. Applicable national adoption, EMC, connector and cooling requirements must be determined with the target-market compliance team. [5]
IEC 62368-1 提供安全框架;本文件未重製其規範要求,亦不宣稱取得認證。目標市場的國家採用版本、EMC、連接器及冷卻要求須由合規團隊判定。[5]